Reduced-flammability, low-smoke power cable with Al conductors
AVVGng(A)-LS — aluminium power cable in low-fire-hazard PVC (ng — does not propagate flame, category A) with low smoke and gas emission (LS — Low Smoke). Used for distribution networks in places with large numbers of people where fire safety is required.
The geometry is identical to AVVG; the difference is the PVC compound formulation — reduced flammability and smoke emission. Full range of cross-sections: 2.5 — 1000 mm².
| Type / size | Cores | Cross-section, mm² | IEC equivalent | Outer Ø, mm | Weight, kg/km | Current (in air), A |
|---|---|---|---|---|---|---|
| AVVGng(A)-LS 3×16 | 3 | 16 | — | 19.2 | 384 | 61 |
| AVVGng(A)-LS 3×25 | 3 | 25 | — | 22.7 | 539 | 78 |
| AVVGng(A)-LS 3×35 | 3 | 35 | — | 25.1 | 672 | 96 |
| AVVGng(A)-LS 3×50 | 3 | 50 | — | 26.6 | 877 | 117 |
| AVVGng(A)-LS 3×70 | 3 | 70 | — | 29.6 | 1121 | 150 |
| AVVGng(A)-LS 3×95 | 3 | 95 | — | 34.1 | 1495 | 183 |
| AVVGng(A)-LS 3×120 | 3 | 120 | — | 36.9 | 1777 | 212 |
| AVVGng(A)-LS 3×150 | 3 | 150 | — | 40.8 | 2173 | 245 |
| AVVGng(A)-LS 3×185 | 3 | 185 | — | 45.3 | 2670 | 280 |
| AVVGng(A)-LS 3×240 | 3 | 240 | — | 50.5 | 3355 | 330 |
| AVVGng(A)-LS 3×300 | 3 | 300 | — | 56.1 | 3924 | 381 |
| AVVGng(A)-LS 4×16 | 4 | 16 | — | 21 | 475 | 61 |
| AVVGng(A)-LS 4×25 | 4 | 25 | — | 25 | 674 | 78 |
| AVVGng(A)-LS 4×35 | 4 | 35 | — | 27.6 | 846 | 96 |
| AVVGng(A)-LS 4×50 | 4 | 50 | — | 29.3 | 1115 | 117 |
| AVVGng(A)-LS 4×70 | 4 | 70 | — | 33.2 | 1463 | 150 |
| AVVGng(A)-LS 4×95 | 4 | 95 | — | 37.7 | 1913 | 183 |
| AVVGng(A)-LS 4×120 | 4 | 120 | — | 41.3 | 2320 | 212 |
| AVVGng(A)-LS 4×150 | 4 | 150 | — | 45.7 | 2842 | 245 |
| AVVGng(A)-LS 4×185 | 4 | 185 | — | 50.2 | 3441 | 280 |
| AVVGng(A)-LS 4×240 | 4 | 240 | — | 56.5 | 4390 | 330 |
AVVGng(A)-LS is a modification of AVVG for facilities with increased fire safety requirements, while retaining the savings provided by aluminium conductors. The insulation and sheath are made of low-fire-hazard PVC compounds with low smoke and gas emission.
Designation breakdown: ng — does not propagate flame in bunched installation (category A — the most stringent); LS (Low Smoke) — when burning, emits 5-7 times less smoke than conventional PVC. Used in schools, hospitals, shopping malls, high-rise buildings and metro — wherever both fire safety and savings on conductor material matter.
Conductors
Stranded aluminium, round or sector-shaped.
Insulation
Low-fire-hazard PVC compound (ng, category A).
Stranding
The insulated cores are stranded into a core, with a tape wrapping where required.
Sheath
Low-fire-hazard PVC compound with low smoke and gas emission (LS).
Cross-section of AVVGng(A)-LS – Al conductors in reduced-flammability PVC
Full product range – see the TCG datasheet
Specify the cross-section and quantity and we will prepare a proposal within 1 business day.
Our HR specialist will contact you within two business days
Send us a request and we will prepare a commercial proposal within 1 business day
Describe your task and we will calculate and send a proposal within 1 business day