Cable finder
+998 (97) 748-80-00 +998 (71) 287-42-42 info@tcg.uz
APvVGng(A)-LS Al + ng-LS
Power cables 1 kV • Al+XLPE + armoured GOST 31996-2012

APVVGNG(A)-LS

Power cable with Al conductors, XLPE and low-flammability PVC

APvVGng(A)-LS is an aluminium power cable with XLPE insulation and a low-fire-hazard PVC sheath (ng — does not propagate flame, category A) with low smoke and gas emission (LS — Low Smoke). The most economical solution for distribution networks in places with large numbers of people.

Voltage 0.66/1 kV
Conductor Aluminium
Insulation XLPE + PVC ng, LS
Cross-section 2.5 – 1000 mm²

APvVGng(A)-LS PRODUCT RANGE

The geometry is identical to APvVG; the difference is in the composition of the outer-sheath PVC compound. Full range of cross-sections: 2.5 — 1000 mm².

Type / sizeCoresCross-section, mm²IEC equivalentOuter Ø, mmWeight, kg/kmCurrent (in air), A
APvVGng(A)-LS 3×16316—17.832177
APvVGng(A)-LS 3×25325—21.345797
APvVGng(A)-LS 3×35335—23.7579120
APvVGng(A)-LS 3×50350—24.9746146
APvVGng(A)-LS 3×70370—28.4987187
APvVGng(A)-LS 3×95395—321286227
APvVGng(A)-LS 3×1203120—35.31569263
APvVGng(A)-LS 3×1503150—39.21925304
APvVGng(A)-LS 3×1853185—43.62377347
APvVGng(A)-LS 3×2403240—48.42972409
APvVGng(A)-LS 3×3003300—53.63495471
APvVGng(A)-LS 4×16416—19.539477
APvVGng(A)-LS 4×25425—23.456797
APvVGng(A)-LS 4×35435—26.1724120
APvVGng(A)-LS 4×50450—27.5944146
APvVGng(A)-LS 4×70470—31.81286187
APvVGng(A)-LS 4×95495—35.41639227
APvVGng(A)-LS 4×1204120—392008263
APvVGng(A)-LS 4×1504150—43.82514304
APvVGng(A)-LS 4×1854185—48.33054347
APvVGng(A)-LS 4×2404240—54.23884409
Complies with GOST 31565-2012 for low-fire-hazard cables.

APvVGng(A)-LS cable description

APvVGng(A)-LS is a modification of APvVG for facilities with stricter fire safety requirements, while retaining maximum economy thanks to the aluminium conductors. Cross-linked polyethylene insulation (with a thermal rating of +90°C) is combined with a sheath of low-fire-hazard, low-smoke PVC compound.

Used in the trunk distribution networks of hospitals, schools, shopping malls, metro systems and high-rise buildings — wherever fire safety, high currents and savings on conductor material are all required. For example: supplying the power equipment of a shopping mall from the central substation.

Applications

Trunk distribution networks in places with large numbers of people
Shopping malls, metro, high-rise buildings – supply to power loads
Power supply to critical high-current loads
Bunched installation of cable lines
Replacement for standard APvVG in locations with a fire risk

Construction

1

Conductors

Stranded aluminium.

2

Insulation

Cross-linked polyethylene (XLPE), +90°C continuous.

3

Stranding

The insulated cores are laid up into a cable core, with tape wrapping where required.

4

Sheath

Low-fire-hazard PVC compound with low smoke and gas emission (LS).

Cross-section of APvVGng(A)-LS – Al cores in XLPE + low-flammability PVC

Technical specifications

Rated voltage 0.66 / 1 kV
Conductor material Aluminium
Insulation Cross-linked polyethylene (XLPE)
Sheath Low-fire-hazard, low-smoke PVC compound (LS)
Flame propagation Does not propagate, category A
Number of cores 1, 2, 3, 4, 5
Cross-sections 2.5 – 1000 mm²
Max. conductor t° (continuous) +90°C
Smoke emission 5–7 times lower vs standard PVC
Standard GOST 31996-2012, GOST 31565-2012

Full product range – see the TCG datasheet

Operating conditions

Installation temperature not below -20°C
Operating temperature -50°C … +50°C
Max. conductor t° (continuous) +90°C
Max. conductor t° (short circuit) +250°C
Air humidity up to 98% at +35°C
Min. bending radius 7.5 × Ø (single-core), 12 × Ø (multi-core)
Service life at least 30 years
Warranty 5 years
Climatic category UHL

DOCUMENTS

REQUEST A PRICE

Specify the cross-section and quantity and we will prepare a proposal within 1 business day.