Cable finder
+998 (97) 748-80-00 +998 (71) 287-42-42 info@tcg.uz
VVG Popular
Power cables 1 kV • Cu+PVC + armoured IEC: NYY

VVG

0.66/1 kV power cable with copper conductors and PVC insulation

VVG — power cable with stranded copper conductors, PVC compound insulation and sheath, without a protective covering. Used for the transmission and distribution of electricity in fixed installations up to 1 kV — in cable structures, indoor premises and on cable racks. Designation breakdown: V — PVC insulation, V — PVC sheath, G — unarmoured.

Voltage 0.66/1 kV
Conductor Copper
Cores 1 – 5
Cross-section 1.5 – 800 mm²

VVG PRODUCT RANGE

Sizes with actual technical specifications: outer diameter, weight, continuous current-carrying capacity (in air at +25°C). Full range of cross-sections per GOST 31996-2012: 1.5 — 800 mm².

Type / sizeCoresCross-section, mm²IEC equivalentOuter Ø, mmWeight, kg/kmCurrent (in air), A
VVG 3×1.531.5NYY1114718.5
VVG 3×2.532.5NYY1218825
VVG 3×434NYY1426334
VVG 3×636NYY15.233543
VVG 3×10310NYY1746960
VVG 3×16316NYY19.266180
VVG 3×25325NYY22.7972101
VVG 3×35335NYY25.11278126
VVG 3×50350NYY26.61742153
VVG 3×70370NYY29.62332196
VVG 3×95395NYY34.13138238
VVG 3×1203120NYY36.93853276
VVG 3×1503150NYY40.84768319
VVG 3×1853185NYY45.35870364
VVG 3×2403240NYY50.57506430
VVG 4×2.542.5NYY12.922925
VVG 4×444NYY15.232634
VVG 4×646NYY16.541943
VVG 4×10410NYY18.659360
VVG 4×16416NYY2184480
VVG 4×25425NYY251251101
VVG 4×35435NYY27.61653126
VVG 4×50450NYY29.32268153
VVG 4×70470NYY33.23078196
VVG 4×95495NYY37.74104238
VVG 4×1204120NYY41.35088276
VVG 4×1504150NYY45.76301319
VVG 5×2.552.5NYY13.526725
VVG 5×454NYY15.938434
VVG 5×656NYY17.349743
VVG 5×10510NYY19.671060
VVG 5×16516NYY22.2101980
Data are given for three-core and four-core cables. Single-, two- and five-core cables can be manufactured on request.

VVG cable description

VVG is the most widely used power cable in Uzbekistan for fixed electrical installations. Stranded copper conductors (1, 2, 3, 4 or 5 cores) are insulated with colour-coded PVC compound. On the outside — a common PVC sheath, without a protective covering. Conductor cross-section: from 1.5 to 800 mm². Rated voltage: 0.66 / 1 kV at a frequency of 50 Hz.

Advantages: long service life (≥30 years), wide temperature range (-50…+50°C), resistance to weathering, easy installation. Not intended for installation in the ground without additional protection — choose VBShv for that.

Applications

Transmission and distribution of electricity in fixed installations up to 1 kV
Installation of single cable lines in cable structures and indoor premises
Electrical wiring in residential and public buildings
Bunched installation on cable racks and in cable galleries
Indoor and outdoor electrical installations

Construction

1

Conductors

Stranded copper, round or sector-shaped, 1, 2, 3, 4 or 5 cores.

2

Insulation

Polyvinyl chloride compound, applied to each core with colour coding.

3

Stranding

The insulated cores are stranded into the cable core.

4

Sheath

Polyvinyl chloride compound, black. Without a protective covering.

Cross-section of 3-core VVG (copper conductors in PVC insulation)

Technical specifications

Rated voltage 0.66 / 1 kV
Conductor material Copper
Conductor class 1 (solid) or 2 (stranded)
Insulation PVC compound
Sheath PVC compound
Number of cores 1, 2, 3, 4, 5
Cross-sections 1.5 – 800 mm²
IEC equivalent NYY
Standard GOST 31996-2012

Full product range – see the TCG datasheet

Operating conditions

Installation temperature not below -15°C
Operating temperature -50°C … +50°C
Max. conductor t° (continuous) +70°C
Max. conductor t° (short circuit) +160°C
Air humidity up to 98% at +35°C
Min. bending radius 10 × Ø
Service life at least 30 years
Warranty 5 years
Climatic category UHL

DOCUMENTS

REQUEST A PRICE