Cable finder
+998 (97) 748-80-00 +998 (71) 287-42-42 info@tcg.uz
VVGng(A)-FRLS FR + LS
Power cables 1 kV • fire-resistant GOST R 53316

VVGNG(A)-FRLS

Fire-resistant power cable with copper conductors and a mica fire barrier

VVGng(A)-FRLS — fire-resistant power cable with copper conductors, a mica-containing fire barrier, and insulation and sheath of low-fire-hazard PVC compound. Maintains circuit integrity under fire for at least 90 minutes at a temperature of 750°C per GOST R 53316. Used in fire protection systems, emergency lighting, firefighting lifts and at facilities with large numbers of people. Designation breakdown: FR — Fire Resistant, ng(A) — does not propagate flame, category A, LS — Low Smoke (low smoke emission).

Voltage 0.66/1 kV
Conductor Copper
Fire resistance FR + ng(A) + LS
Cross-section 1.5 – 1000 mm²

VVGng(A)-FRLS PRODUCT RANGE

Sizes with actual technical specifications. The geometry is similar to VVG; fire resistance is provided by the mica fire barrier and the PVC formulation.

Type / sizeCoresCross-section, mm²IEC equivalentOuter Ø, mmWeight, kg/kmCurrent (in air), A
VVGng(A)-FRLS 3×1.531.5—1114718.5
VVGng(A)-FRLS 3×2.532.5—1218825
VVGng(A)-FRLS 3×434—1426334
VVGng(A)-FRLS 3×636—15.233543
VVGng(A)-FRLS 3×10310—1746960
VVGng(A)-FRLS 3×16316—19.266180
VVGng(A)-FRLS 3×25325—22.7972101
VVGng(A)-FRLS 3×35335—25.11278126
VVGng(A)-FRLS 3×50350—26.61742153
VVGng(A)-FRLS 3×70370—29.62332196
VVGng(A)-FRLS 3×95395—34.13138238
VVGng(A)-FRLS 3×1203120—36.93853276
VVGng(A)-FRLS 3×1503150—40.84768319
VVGng(A)-FRLS 3×1853185—45.35870364
VVGng(A)-FRLS 3×2403240—50.57506430
VVGng(A)-FRLS 4×2.542.5—12.922925
VVGng(A)-FRLS 4×444—15.232634
VVGng(A)-FRLS 4×646—16.541943
VVGng(A)-FRLS 4×10410—18.659360
VVGng(A)-FRLS 4×16416—2184480
VVGng(A)-FRLS 4×25425—251251101
VVGng(A)-FRLS 4×35435—27.61653126
VVGng(A)-FRLS 4×50450—29.32268153
VVGng(A)-FRLS 4×70470—33.23078196
VVGng(A)-FRLS 4×95495—37.74104238
VVGng(A)-FRLS 4×1204120—41.35088276
VVGng(A)-FRLS 4×1504150—45.76301319
The cables meet the requirements of Federal Law No. 123-FZ “Technical Regulations on Fire Safety Requirements” for class P1a fire protection systems.

VVGng(A)-FRLS cable description

VVGng(A)-FRLS — fire-resistant power cable for critical loads that must keep operating even during a fire. These include automatic fire suppression and smoke extraction systems, emergency lighting, evacuation lifts and sprinkler system pumps.

How it works: around each conductor is wound a tape containing mica — a mineral with a melting point above 1300°C. When conventional PVC insulation breaks down in fire, the mica layer remains intact and continues to insulate the conductor. Per GOST R 53316, the cable must maintain circuit integrity at 750°C for at least 90 minutes — enough time to evacuate people and extinguish the fire.

In addition, the insulation and sheath are made of low-fire-hazard PVC (ng, category A) with low smoke and gas emission (LS) — this reduces smoke toxicity and improves visibility on escape routes.

Applications

Automatic fire protection and smoke extraction systems
Emergency lighting and escape routes
Firefighting lifts, fire pumps
Facilities with large numbers of people: hospitals, schools, shopping malls, metro
High-rise buildings and underground structures

Construction

1

Conductors

Stranded copper, round or sector-shaped, 1, 2, 3, 4 or 5 cores.

2

Fire barrier

Mica-containing tape applied over each conductor. Maintains the integrity of the insulation at a fire temperature of ≥ 750°C for at least 90 minutes.

3

Insulation

Low-fire-hazard PVC compound, with colour coding of the cores.

4

Stranding

The insulated cores are stranded into a core.

5

Sheath

Low-fire-hazard PVC compound with low smoke and gas emission (LS – Low Smoke). Orange – the standard colour for fire-resistant cables.

Cross-section of VVGng(A)-FRLS – orange low-fire-hazard sheath, golden mica tape around each conductor

Technical specifications

Rated voltage 0.66 / 1 kV (up to 3 kV)
Conductor material Copper
Fire barrier Mica-containing tape
Insulation Low-fire-hazard PVC compound
Sheath Low-fire-hazard PVC compound (LS)
Fire resistance (FR) ≥ 90 min at 750°C per GOST R 53316
Flame propagation Does not propagate, category A
Smoke emission Reduced 5–7 times vs standard PVC
Number of cores 1, 2, 3, 4, 5
Cross-sections 1.5 – 1000 mm²
Standards GOST 31996-2012, GOST 31565-2012, GOST R 53316

Full product range – see the TCG datasheet

Operating conditions

Installation temperature not below -15°C
Operating temperature -50°C … +50°C
Max. conductor t° (continuous) +70°C
Max. conductor t° (short circuit) +160°C
Fire resistance ≥ 750°C for 90 minutes
Air humidity up to 98% at +35°C
Min. bending radius 10 × Ø
Service life at least 30 years
Warranty 5 years

DOCUMENTS

REQUEST A PRICE

Specify the cross-section and quantity and we will prepare a proposal within 1 business day.