Cable finder
+998 (97) 748-80-00 +998 (71) 287-42-42 info@tcg.uz
APvP XLPE + PE
Power cables 6/10/35 kV IEC: NA2XSE2Y

APVP

6-35 kV power cable with aluminium conductors, XLPE insulation and PE sheath

APvP is a medium-voltage power cable with an aluminium conductor, cross-linked polyethylene (XLPE) insulation and an outer sheath of polyethylene (PE). The main difference from APvV is the PE outer sheath instead of PVC. PE offers better moisture resistance and mechanical strength and is suitable for installation in high-humidity conditions. Designation breakdown: APv – Al, XLPE insulation, P – PE sheath.

Voltage 6 / 10 / 15 / 20 / 35 kV
Conductor Aluminium
Sheath Polyethylene (PE)
Cross-section 25 – 800 mm²

APvP PRODUCT RANGE (for 6/10 kV)

Sizes for 6/10 kV. 3.6/6, 8.7/15, 12/20 and 18/30 kV versions are also produced.

Type / sizeCoresCross-section, mm²VoltageCopper screen, mm²Outer Ø, mmWeight, kg/km
APvP 1×251256/10 kV16——
APvP 1×351356/10 kV16——
APvP 1×501506/10 kV16——
APvP 1×701706/10 kV16——
APvP 1×951956/10 kV16——
APvP 1×12011206/10 kV16——
APvP 1×15011506/10 kV16——
APvP 1×18511856/10 kV16——
APvP 1×24012406/10 kV25——
Exact parameters – see the TCG datasheet.

APvP cable description

APvP is a version of APvV with a polyethylene outer sheath instead of PVC. The polyethylene sheath performs better in terms of moisture resistance, mechanical strength and chemical resistance, but worse in terms of fire safety (ordinary PE is a combustible material). It is used in conditions where moisture and mechanical loads matter more than fire-safety requirements: underground tunnels with standing water, installation in chemically aggressive environments, and operation in regions with high air humidity.

Versions with a reinforced polyethylene outer sheath (APvPu) are also produced – see the corresponding product pages.

Applications

6-35 kV distribution networks in high-humidity premises
Installation in ducts and tunnels at risk of water ingress
Use in locations where a PVC sheath does not provide sufficient moisture protection
Trunk interconnection lines in highly chemically aggressive atmospheres
Used in groups of 3 single-core cables

Construction

1

Conductor

Aluminium, stranded, round, compacted.

2

Semi-conducting conductor screen

Electrically conductive cross-linked polymer compound.

3

Insulation

Cross-linked polyethylene (XLPE).

4

Semi-conducting insulation screen

5

Copper wire screen

Copper wires + helical tape.

6

Outer sheath

Polyethylene (PE), black. Improved moisture resistance.

APvP cross-section – aluminium conductor, XLPE, copper wire screen, PE sheath

Technical specifications

Rated voltage 6 / 10 / 15 / 20 / 35 kV
Conductor material Aluminium
Insulation Cross-linked polyethylene (XLPE)
Sheath Polyethylene (PE)
Moisture resistance Enhanced (PE vs PVC)
Number of cores 1 (typical) or 3
Cross-sections 25 – 800 mm²
Standard GOST R 55025-2012 / O'z DSt IEC 60502-2

Detailed specifications – see the TCG datasheet

Operating conditions

Installation temperature not below -20°C
Operating temperature -30°C … +50°C (cables with PE sheath)
Max. conductor t° (continuous) +90°C
Max. conductor t° (short circuit) +250°C
Air humidity up to 98% at +35°C
Min. bending radius 15 × Ø (single-core), 25 × Ø (three-core)
Service life at least 30 years
Warranty 5 years
Climatic category UHL

DOCUMENTS

REQUEST A PRICE

Specify the cross-section and quantity and we will prepare a proposal within 1 business day.