PvV 6-35 kV
Power cables 6/10/35 kV IEC: N2XSE2Y

PVV

6-35 kV power cable with copper conductors and XLPE insulation

PvV is a medium-voltage power cable with a copper conductor, cross-linked polyethylene (XLPE) insulation, semi-conducting screens and a PVC compound sheath. It is used in 6, 10, 15, 20 and 35 kV distribution networks. It is installed as a group of three single-core cables (one per phase) in cable structures and indoor premises. Designation breakdown: Pv – XLPE insulation, V – PVC sheath.

Voltage 6 / 10 / 15 / 20 / 35 kV
Conductor Copper
Insulation XLPE 3.4 mm (for 6/10 kV)
Cross-section 16 – 800 mm²

PvV PRODUCT RANGE (for 6/10 kV)

Sizes of single-core cables rated 6/10 kV – the most common voltage in Uzbekistan's distribution networks. Actual technical specifications: outer diameter, weight, continuous current-carrying capacity in air.

Type / sizeCoresCross-section, mm²VoltageCopper screen, mm²Outer Ø, mmWeight, kg/kmCurrent (in air), A
PvV 1×161166/10 kV1618.3457128
PvV 1×251256/10 kV1619.6551167
PvV 1×351356/10 kV1620.6646203
PvV 1×501506/10 kV1622.1789243
PvV 1×701706/10 kV1623.6969303
PvV 1×951956/10 kV1625.41194369
PvV 1×12011206/10 kV1626.91417426
PvV 1×15011506/10 kV2528.91751481
PvV 1×18511856/10 kV2530.82074550
PvV 1×24012406/10 kV2533.22543647
PvV 1×30013006/10 kV2535.53049739
PvV 1×40014006/10 kV35393958837
PvV 1×50015006/10 kV3542.44821942
PvV 1×63016306/10 kV3545.758871064
The table is given for 6/10 kV as the most common voltage in distribution networks. Versions for 3.6/6, 8.7/15, 12/20 and 18/30 kV are also produced – they differ in insulation thickness and overall dimensions.

PvV cable description

PvV is a modern power cable for overhead and underground medium-voltage lines of 6, 10, 15, 20 and 35 kV. Construction: stranded copper conductor, cross-linked polyethylene (XLPE) insulation, semi-conducting screens to equalise the electric field, a copper wire screen to carry away leakage currents, and a PVC compound outer sheath.

Advantages of XLPE for MV cables: long service life (30+ years even under high-voltage conditions), overload resistance, lower dielectric losses vs paper insulation. It is typically used in groups of 3 single-core cables (one per phase). For three-core versions, see PvVng or PvBV.

Applications

6, 10, 15, 20 and 35 kV distribution networks
Installation in cable structures, indoor premises, on cable racks and in tunnels
Power supply to transformer substations and distribution points
Power supply to large industrial consumers
Used in groups of 3 single-core cables (one per phase)

Construction

1

Conductor

Stranded copper, round, compacted. Cross-section 16-800 mm².

2

Extruded semi-conducting conductor screen

A layer of conductive cross-linked polymer compound that equalises the electric field.

3

Insulation

Cross-linked polyethylene (XLPE). Thickness depends on voltage: 3.4 mm for 6/10 kV; 4.5 mm for 15 kV; 5.5 mm for 20 kV; 8.0 mm for 35 kV.

4

Extruded semi-conducting insulation screen

Similar to the conductor screen, equalises the field.

5

Conductive tape

Over the semi-conducting screen.

6

Copper wire screen

Copper wires over the conductive tape, with a helically wound copper tape on top. Screen cross-section 16 mm² (for 16-185 mm² conductors) or 25-35 mm² (for larger cross-sections).

7

Inner sheath (bedding)

An extruded layer of polymer compound.

8

Outer sheath

PVC compound, black.

Cross-section of PvV – Cu conductor, semi-conducting screen, XLPE insulation, copper wire screen, PVC sheath

Technical specifications

Rated voltage 6 / 10 / 15 / 20 / 35 kV
Conductor material Copper
Conductor class 1 or 2 per GOST 22483
Insulation Cross-linked polyethylene (XLPE)
Semi-conducting screens Over the conductor and over the insulation
Copper wire screen 16 / 25 / 35 mm² (depends on conductor cross-section)
Sheath PVC compound
Number of cores 1 (typical) or 3
Cross-sections 16 – 800 mm²
IEC equivalent N2XSE2Y
Standard GOST R 55025-2012 / O'z DSt IEC 60502-2

Full product range (all voltages 6-35 kV) – see the TCG datasheet

Operating conditions

Installation temperature not below -20°C
Operating temperature -50°C … +50°C
Max. conductor t° (continuous) +90°C
Max. conductor t° (short circuit) +250°C
Air humidity up to 98% at +35°C
Min. bending radius 15 × Ø (single-core), 25 × Ø (three-core)
Service life at least 30 years
Warranty 5 years
Climatic category UHL