PuGV High flexibility
Installation wires GOST 31947-2012

PUGV

High-flexibility installation wire with copper conductor

PuGV is a high-flexibility installation wire with a stranded copper conductor of flexibility class 5 in PVC insulation. It is used for wiring with bends, connection to movable terminals and in vibration conditions. Designation breakdown: Pu – installation, G – flexible, V – PVC.

Voltage 450/750 V
Conductor Copper, flexibility class 5
Cross-section 0.50 – 400 mm²
Standard GOST 31947-2012

PuGV PRODUCT RANGE

Sizes with technical specifications.

TypeNumber of wiresConductor ⌀, mmInsulation thickness, mmOuter ⌀, mmWeight, kg/km
PuGV 0.5160.920.62.19
PuGV 0.75241.130.62.313
PuGV 1321.300.72.717
PuGV 1.5301.600.73.022
PuGV 2.5502.000.83.635
PuGV 4562.550.84.152
PuGV 6843.000.84.672
PuGV 10804.201.06.2118
PuGV 161265.301.07.3176
PuGV 251966.701.29.1265
PuGV 352768.001.210.4360
PuGV 503969.501.412.3490
PuGV 7036011.601.414.4682
PuGV 9547513.501.616.7920
PuGV 12060815.201.618.41160
PuGV 15075616.801.820.41446
PuGV 18592518.902.022.91800
PuGV 240122121.702.226.12340
Data are given for standard cross-sections per GOST 31947-2012 (for APuV/PuV/PuGV) and TCG TS (for VPP/VPV). Exact parameters of a batch are given in the datasheet. Intermediate cross-sections and special insulation colours can be manufactured to order.

PuGV wire description

PuGV is a flexible installation wire for wiring in conditions that require frequent bending and re-routing. Class 5 per GOST 22483 provides sufficient flexibility: a minimum bending radius of just 3ר (compared with 6ר for rigid PuV).

It is used for wiring in control cabinets and automation panels, in electrical equipment with movable terminals and in vibration conditions. The optimal choice for jumpers between terminal blocks and devices inside cabinets. Not intended for fixed installation in walls – ordinary PuV is used there.

Applications

Wiring of electrical installations with frequent bending of wires
Control circuits connected to movable terminals
Wiring in vibration conditions (control panels, automation cabinets)
Internal wiring of electrical equipment
Jumpers between terminal blocks and devices

Construction

1

Conductor

Stranded copper of flexibility class 5 per GOST 22483. A large number of fine wires (up to 1200 and more for the larger cross-sections) provides high flexibility under repeated bending.

2

Insulation

High-elasticity PVC compound with colour coding.

PuGV cross-section – stranded copper conductor of flexibility class 5 in PVC insulation

Technical specifications

Rated voltage 450/750 V
Frequency up to 400 Hz
DC voltage up to 1000 V
Conductor material Copper
Conductor class 5 (flexible, GOST 22483)
Insulation High-elasticity PVC compound
Cross-sections 0.50 – 400 mm²
Min. bending radius 3 × Ø
Standard GOST 31947-2012

Detailed specifications – see the TCG datasheet

Operating conditions

Installation temperature not below -15°C
Operating temperature -40°C … +60°C
Max. conductor t° (continuous) +70°C
Air humidity up to 98% at +35°C
Min. bending radius 6 × Ø (class 1-2), 3 × Ø (class 5)
Service life at least 30 years
Warranty 5 years