In a cable type designation, the insulation material comes right after the conductor material: V stands for PVC compound, Pv for cross-linked polyethylene. For more about the letters, see the article “How to read a power cable type designation”. For example, VVG and PvVG are 1 kV copper power cables of the same design, and they differ only in their insulation.
How the materials differ
PVC compound is a thermoplastic: it softens when heated. Cross-linked polyethylene is produced by chemically cross-linking polyethylene. After cross-linking, the material becomes thermosetting: it does not melt when heated and keeps its shape.
Permissible conductor temperatures
GOST 31996-2012 sets the maximum conductor temperature depending on the insulation material. The first value is for PVC, the second for XLPE:
- continuous operation — 70 and 90 °C;
- overload — 90 and 130 °C;
- short circuit — up to 160 and up to 250 °C;
- limit for non-ignition of the cable during a short circuit — 350 and 400 °C.
The higher the permissible temperature, the more current a conductor of the same cross-section can carry. That is why a cable with XLPE insulation has a higher current-carrying capacity and copes better with overloads and short circuits.
The standard sets the same values as for PVC for insulation made of halogen-free polymer compounds, and the XLPE values for cross-linked halogen-free compounds.
Where each is used
- Cables with PVC insulation, such as VVGng(A)-LS, are installed in buildings, in cable structures and on cable racks.
- XLPE is chosen when current-carrying capacity matters. For example, the armoured APvBShv is used for 0.4 kV trunk lines laid in the ground.
- 6–35 kV cables in the TCG catalogue are made only with XLPE insulation, for example PvBVng(A).
Fire safety
PVC contains chlorine, so it emits corrosive gases when burning. Polyethylene contains no halogens, but it is combustible. If a cable that does not propagate flame is needed, the ng(A) version is chosen. For example, PvVGng(A)-LS has XLPE insulation and a sheath of low-fire-hazard PVC compound. Where halogens are not permitted, halogen-free cables are used, for example PvPGng(A)-HF.
TCG engineers can help you choose the insulation for your installation conditions and load. Send us your project design or specification.