The letter code for 0.66, 1 and 3 kV power cables is set by the interstate standard GOST 31996-2012. These are GOST designations, not IEC or VDE codes; below, each letter is given in Latin transliteration, as in the type names on our site, with the original Cyrillic letter in brackets. The letters follow the order of the cable's construction:
- conductor material;
- insulation;
- sheath;
- armour, or the lack of it;
- protective outer sheath;
- fire safety version.
Conductor
- A (А) — aluminium conductors: AVVG, APvBShv.
- As (Ас) — aluminium alloy conductors.
- If there is no letter, the conductors are copper: VVG, PvVG.
Insulation
- V (В) — polyvinyl chloride compound (PVC), including low-fire-hazard compound.
- Pv (Пв) — cross-linked polyethylene (XLPE).
- P (П) — halogen-free polymer compound.
The insulation determines the permissible conductor temperature. Under GOST 31996-2012, it is 70 °C in continuous operation for PVC and 90 °C for XLPE. That is why a cable with XLPE insulation has a higher current-carrying capacity.
Sheath, armour and outer sheath
- V in the second position — PVC sheath.
- G (Г) — unarmoured cable. In VVG: PVC insulation, PVC sheath, no armour.
- B (Б) — armour of galvanised steel tapes.
- Ba (Ба) — armour of aluminium or aluminium alloy tapes.
- K (К) — armour of round galvanised steel wires.
- Shv (Шв) — PVC protective outer sheath over the armour, as in VBShv.
- Shp (Шп) — polyethylene protective outer sheath.
Fire safety
The main part of the designation is followed by the fire safety index:
- ng(A) (нг(А)) — the cable does not propagate flame in bunched installation, i.e. when laid in a bundle, under test category A;
- LS (low smoke) — reduced smoke and gas emission;
- HF (halogen free) — emits no corrosive gases when burning or smouldering;
- FR (fire resistant) — maintains circuit integrity in a fire for the time specified for the cable type;
- LTx (low toxicity) — low toxicity of combustion products.
The indices can be combined: ng(A)-LS, ng(A)-FRLS, ng(A)-HF, ng(A)-FRHF, ng(A)-LSLTx. Cable fire hazard classes are established by GOST 31565-2012. Which version is required at a given facility is determined by the project design in line with fire safety requirements.
Cores and voltage
The type is followed by the number of cores and their cross-section, then, after a hyphen, the voltage. An example from GOST 31996-2012:
AVVGng(A)-LS 3×70os+1×35os(N)-1
- three cores with a cross-section of 70 mm² and one of 35 mm²;
- o (о) — solid conductor, m (м) — stranded conductor;
- s (с) — sector-shaped, k (к) — round;
- (N) — neutral core, (PE) — earthing core;
- 1 — rated voltage of 1 kV.
For conductors up to 10 mm², the conductor type may be omitted.
Three types from the TCG catalogue
- VVGng(A)-LS:
- copper conductors;
- insulation and sheath of low-fire-hazard PVC compound;
- unarmoured;
- does not propagate flame in a bundle; reduced smoke and gas emission.
- APvBShv:
- aluminium conductors;
- XLPE insulation;
- steel tape armour;
- PVC protective outer sheath.
- PPGng(A)-FRHF:
- copper conductors;
- insulation and sheath of halogen-free compounds;
- unarmoured;
- fire-resistant, does not propagate flame and emits no corrosive gases.
Wires, as well as medium-voltage cables, are designated under their own standards. For self-supporting wires, see the article “SIP-1, SIP-2, SIP-3, SIP-4: how they differ”.
If your project design specifies a type that is not in the catalogue, or you need an equivalent, send us the specification. TCG engineers will select the cable.