SIP-1, SIP-2, SIP-3, SIP-4: how self-supporting insulated wire types differ

Self-supporting insulated wire (SIP) is fixed directly to poles, without insulators or cross-arms. The types differ in how the load-bearing element is designed and in the voltage the wire is rated for.
SIP-4 wire with four aluminium conductors, 3D model

SIP types and their designations are set by the interstate standard GOST 31946-2012.

What all types have in common

  • The insulation is made of UV-stabilised cross-linked polyethylene or a self-extinguishing cross-linked compound. It does not degrade in sunlight.
  • The main conductors are stranded from round aluminium wires.
  • The messenger is made of aluminium alloy wires with a tensile strength of at least 295 N/mm².
  • The wires operate at ambient temperatures from -60 to +50 °C.

The number in the type: wire design

  • SIP-1 — with an uninsulated neutral messenger. The phase cores are insulated, while the aluminium alloy messenger is left bare. This is what the wire hangs from.
  • SIP-2 — with an insulated neutral messenger. All cores are insulated, including the messenger.
  • SIP-3 — covered conductor. A single aluminium alloy conductor in a protective covering of cross-linked polyethylene. Intended for 10–20 and 35 kV lines. The protective covering reduces the risk of a short circuit when branches touch the line or conductors clash.
  • SIP-4 — no messenger. Two or four insulated cores are stranded together and carry the load jointly.

SIP-1, SIP-2 and SIP-4 are rated for voltages up to 0.6/1 kV, i.e. for 0.4 kV networks.

Letters in the type

  • n (н) — does not propagate flame and does not form flaming droplets: SIPn-1, SIPn-2, SIPn-3, SIPn-4.
  • g (г) — sealed (water-blocked). A water-blocking element stops moisture from spreading along the conductor if the insulation is damaged: SIPg-3.
  • st (ст) — the messenger is reinforced with steel wire. This index is not in GOST 31946-2012; it is introduced by the manufacturer's technical specifications. In the TCG catalogue, these are SIPst-2 and SIPst-3.

How to read the full designation

The type is followed by the number of cores and their cross-section, then, after a hyphen, the voltage. Examples from GOST 31946-2012:

  • SIP-2 3×70+1×95-0.6/1 — three 70 mm² phase cores, a 95 mm² neutral messenger, voltage 0.6/1 kV.
  • SIP-2 3×70+1×95+2×25-0.6/1 — the same plus two 25 mm² auxiliary cores, for example for street lighting.
  • SIPg-3 1×120-35 — one 120 mm² conductor for 35 kV.

Which type to choose

  • 0.4 kV trunk overhead lines — SIP-2 or SIP-1. The choice is usually set by the grid operator's technical requirements and the project design.
  • Branch from the line to a house — SIP-4: 2×16 for a single-phase service entrance, 4×16 and larger for a three-phase one. The cross-section is selected according to the load.
  • 10–20 and 35 kV overhead lines — SIP-3. In high humidity, near the sea and in polluted atmospheres — SIPg-3.
  • Facades, service entrances into buildings and places with stricter fire safety requirements — types with the “n” index.

All types are in the SIP wires section. If you need a cross-section calculation or a selection for your project, send us a request.

More articles

All articles
Single-core cable with XLPE insulation, 3D model
2 min read

XLPE or PVC: how power cable insulation differs

The insulation determines how hot the conductor may get, and therefore how much current the cable can carry. We compare the two most common materials: PVC compound and cross-linked polyethylene (XLPE).
Five-core copper power cable by TCG, 3D model
3 min read

How to read a power cable type designation

A power cable type designation is read from left to right: the letters describe its layers in turn, from the conductor to the outer sheath. We go through the codes of GOST 31996-2012 using examples from the TCG catalogue.