各规格型号的实际技术参数:外径(含铠装)、重量、空气中长期允许载流量。完整截面范围:2.5~240 mm²。
| 规格型号 | 芯数 | 截面(mm²) | IEC对应型号 | 外径(mm) | 重量(kg/km) | 空气中载流量(A) |
|---|---|---|---|---|---|---|
| VBShvng(A)-FRLS 3×4 | 3 | 4 | — | 14.4 | 321 | 34 |
| VBShvng(A)-FRLS 3×6 | 3 | 6 | — | 15.6 | 399 | 43 |
| VBShvng(A)-FRLS 3×10 | 3 | 10 | — | 17.4 | 541 | 60 |
| VBShvng(A)-FRLS 3×16 | 3 | 16 | — | 19.6 | 744 | 80 |
| VBShvng(A)-FRLS 3×25 | 3 | 25 | — | 23.2 | 1072 | 101 |
| VBShvng(A)-FRLS 3×35 | 3 | 35 | — | 25.5 | 1391 | 126 |
| VBShvng(A)-FRLS 3×50 | 3 | 50 | — | 27 | 1871 | 153 |
| VBShvng(A)-FRLS 3×70 | 3 | 70 | — | 30 | 2480 | 196 |
| VBShvng(A)-FRLS 3×95 | 3 | 95 | — | 35.2 | 3571 | 238 |
| VBShvng(A)-FRLS 3×120 | 3 | 120 | — | 38 | 4325 | 276 |
| VBShvng(A)-FRLS 3×150 | 3 | 150 | — | 41.9 | 5291 | 319 |
| VBShvng(A)-FRLS 3×185 | 3 | 185 | — | 46.3 | 6452 | 364 |
| VBShvng(A)-FRLS 3×240 | 3 | 240 | — | 51.6 | 8162 | 430 |
| VBShvng(A)-FRLS 4×4 | 4 | 4 | — | 15.6 | 389 | 34 |
| VBShvng(A)-FRLS 4×6 | 4 | 6 | — | 16.9 | 489 | 43 |
| VBShvng(A)-FRLS 4×10 | 4 | 10 | — | 19 | 673 | 60 |
| VBShvng(A)-FRLS 4×16 | 4 | 16 | — | 21.4 | 937 | 80 |
| VBShvng(A)-FRLS 4×25 | 4 | 25 | — | 25.4 | 1362 | 101 |
| VBShvng(A)-FRLS 4×35 | 4 | 35 | — | 28.1 | 1778 | 126 |
| VBShvng(A)-FRLS 4×50 | 4 | 50 | — | 29.7 | 2411 | 153 |
| VBShvng(A)-FRLS 4×70 | 4 | 70 | — | 33.6 | 3243 | 196 |
| VBShvng(A)-FRLS 4×95 | 4 | 95 | — | 38.8 | 4585 | 238 |
| VBShvng(A)-FRLS 4×120 | 4 | 120 | — | 42.4 | 5617 | 276 |
| VBShvng(A)-FRLS 4×150 | 4 | 150 | — | 46.8 | 6888 | 319 |
VBShvng(A)-FRLS兼具两项重要性能:满足消防安全系统需要的耐火性能,以及适合直埋敷设的铠装机械防护。其结构包括:每根导体外绕包云母带形成的耐火层、双层镀锌钢带铠装以及阻燃聚氯乙烯(PVC)外护套。
适用于同时要求耐火性能(750°C下90分钟)和机械防护的场合:建筑物之间的电缆路径、隧道、地下停车场、火灾荷载较高的工业企业。符合第123-FZ号联邦法对关键负荷的要求。
导体
铜绞合导体。
耐火层
每根导体外绕包云母带。火灾时保持线路完整性≥ 90分钟。
绝缘
阻燃PVC,线芯采用颜色识别。
成缆及铠装内衬层
绝缘线芯成缆后,外挤包PVC内衬层。
铠装
双层镀锌钢带螺旋绕包,间隙不大于带宽的50%。
外护套
阻燃PVC(LS),橙色。
VBShvng(A)-FRLS横截面示意图:橙色PVC外护套+钢铠装+导体外云母带耐火层
完整规格型号见TCG产品数据表
人事专员将在两个工作日内与您联系。
请提交需求,我们将在1个工作日内为您准备商务报价。
请描述您的需求,我们将在1个工作日内为您核算并发送商务报价。