Cable finder
+998 (97) 748-80-00 +998 (71) 287-42-42 info@tcg.uz
SIPst-2 Trunk OHL
SIP wires IEC: AXKA

SIPST-2

Self-supporting insulated wire with an insulated neutral messenger reinforced with steel wire

Self-supporting insulated wire with three insulated aluminium-alloy conductors and an insulated neutral messenger of aluminium wires reinforced with steel wire (index “st”). Insulation — UV-stabilised cross-linked polyethylene. Used for 0.6/1 kV trunk overhead lines and line branches.

Voltage 0.6/1 kV
Conductor Phases – Al alloy; neutral – Al + steel
Cores 3+1 (phases + insulated neutral)
Cross-section 16–120 mm²

SIPst-2 PRODUCT RANGE

The full list of manufactured cross-sections from the official TCG product range.

Type / sizeCoresNeutral cross-section, mm²IEC equivalentOuter Ø, mmWeight, kg/km
SIPst-2 3×16+1×253+125AXKA19220
SIPst-2 3×25+1×353+135AXKA21.5310
SIPst-2 3×35+1×503+150AXKA24420
SIPst-2 3×50+1×54.63+154.6AXKA26.5540
SIPst-2 3×70+1×703+170AXKA28.5720
SIPst-2 3×95+1×703+170AXKA30.5860
SIPst-2 3×120+1×953+195AXKA341080
Outer diameter and weight are given as typical values per GOST 31946-2012. The exact TCG factory parameters are provided in the product datasheet.

SIPst-2 wire description

SIPst-2 — self-supporting insulated wire for 0.6/1 kV overhead power lines. Construction: three aluminium-alloy phase conductors stranded around an insulated neutral messenger of aluminium wires reinforced with steel wire. All cores are insulated with UV-stabilised cross-linked polyethylene, resistant to ultraviolet radiation and weathering.

Used for 0.4 kV trunk lines, line branches and in areas with heavy ice and wind loads.

Applications

0.4 kV trunk overhead power lines
Lines in areas with heavy ice and wind loads
Line branches from overhead lines
Replacement of bare conductors on overhead lines to improve reliability
Power supply to residential, public and industrial facilities

Construction

1

Phase conductors (3 pcs)

Stranded, compacted, made of aluminium alloy.

2

Insulated neutral messenger

Stranded, made of aluminium wires, reinforced with steel wire. Carries the mechanical load of the entire wire.

3

Insulation

UV-stabilised cross-linked polyethylene, black. Resistant to UV radiation and weathering.

4

Stranding

The three phase cores are stranded around the insulated neutral messenger.

Cross-section of SIPst-2 (3 aluminium-alloy phase cores + insulated neutral messenger reinforced with steel wire)

Technical specifications

Rated voltage 0.6/1 kV
Conductor material Phase conductors – aluminium alloy; neutral messenger – Al wires reinforced with steel wire
Conductor class Stranded, compacted
Insulation UV-stabilised cross-linked polyethylene
Number of cores 3 phase + 1 insulated neutral messenger
Phase conductor cross-sections 16 – 120 mm²
IEC equivalent AXKA
Standard GOST 31946-2012

Detailed specifications (current-carrying capacity, resistance, weight) – to be added once the specifications file is uploaded

Operating conditions

Installation temperature not below -20°C
Operating temperature -60°C … +50°C
Max. conductor t° (continuous) +90°C
Max. conductor t° (short circuit) +250°C
Min. bending radius 10 × Ø
Service life at least 40 years
Warranty 5 years
Climatic category UHL

DOCUMENTS

REQUEST A PRICE

Specify the cross-section and quantity and we will prepare a proposal within 1 business day.