Cable finder
+998 (97) 748-80-00 +998 (71) 287-42-42 info@tcg.uz
PuV Cu + installation
Installation wires GOST 31947-2012

PUV

Installation wire with copper conductor and PVC insulation

PuV is an installation wire with a single copper conductor in PVC insulation. It is the copper counterpart of APuV, with a smaller cross-section for the same current load. It is used for fixed installation in the lighting and power networks of buildings. Designation breakdown: Pu – installation wire, V – PVC.

Voltage 450/750 V
Conductor Copper, class 1-2
Cross-section 1.5 – 400 mm²
Standard GOST 31947-2012

PuV PRODUCT RANGE

Sizes with technical specifications.

TypeNumber of wiresConductor ⌀, mmInsulation thickness, mmOuter ⌀, mmWeight, kg/kmDC resistance, Ω/km
PuV 1.511.400.72.81912.1
PuV 2.511.800.83.4307.41
PuV 412.260.83.9464.61
PuV 612.760.84.4643.08
PuV 1013.571.05.61051.83
PuV 1674.501.06.51571.15
PuV 2575.651.28.12350.727
PuV 3576.701.29.13170.524
PuV 50197.951.410.84320.387
PuV 70199.601.412.46040.268
PuV 951911.201.614.48210.193
PuV 1201912.601.615.810380.153
PuV 1503714.201.817.812950.124
PuV 1853715.802.019.816040.099
PuV 2403718.202.222.620730.075
PuV 3003720.102.424.925950.060
PuV 4006123.202.628.434520.047
Data are given for standard cross-sections per GOST 31947-2012 (for APuV/PuV/PuGV) and TCG TS (for VPP/VPV). Exact parameters of a batch are given in the datasheet. Intermediate cross-sections and special insulation colours can be manufactured to order.

PuV wire description

PuV is the principal copper installation wire for fixed electrical wiring. A single copper conductor in PVC insulation. It has an extremely wide range of applications: from small lighting circuits in housing (1.5-2.5 mm²) to industrial power installations (120-400 mm²).

Advantages vs APuV: a smaller cross-section for the same load (roughly 1-2 sizes down), compatibility with copper terminals without special adapters, and less heating. The drawback is the higher cost due to the copper. In Uzbekistan it is the most widely used wire for networks inside buildings.

Applications

Fixed 0.4 kV lighting and power networks
Electrical wiring of residential, public and industrial buildings
Wiring of electrical installations, machines and mechanisms
Bunched installation in conduits, cable ducts and trays
Sections without bends – fixed installation

Construction

1

Conductor

Copper, solid (cross-sections up to 10 mm²) or stranded (16+ mm²), class 1 or 2 per GOST 22483. Made from KMO copper wire rod of TCG's own production.

2

Insulation

PVC compound with colour coding per GOST.

PuV cross-section – copper conductor in PVC insulation

Technical specifications

Rated voltage 450/750 V
Frequency up to 400 Hz
DC voltage up to 1000 V
Conductor material Copper
Conductor class 1 or 2
Insulation PVC compound
Number of cores 1
Cross-sections 1.5 – 400 mm²
Standard GOST 31947-2012

Detailed specifications – see the TCG datasheet

Operating conditions

Installation temperature not below -15°C
Operating temperature -40°C … +60°C
Max. conductor t° (continuous) +70°C
Air humidity up to 98% at +35°C
Min. bending radius 6 × Ø (class 1-2), 3 × Ø (class 5)
Service life at least 30 years
Warranty 5 years
Climatic category UHL

DOCUMENTS

REQUEST A PRICE

Specify the cross-section and quantity and we will prepare a proposal within 1 business day.